EasyManua.ls Logo

Siemens SICAM Q100 7KG95 Series - Mains Signaling Voltage; Memory Management

Siemens SICAM Q100 7KG95 Series
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 Operating Parameters
16.5 Recording and Reporting
415SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.5.4 Mains Signaling Voltage
16.5.5 Memory Management
Tolerance unit Percentage Percentage
Numerical
Tolerance number Percentage: 3 % of primary
nominal voltage,
Numerical: 0.50 V
1 % to 5 % in 1-% steps
0.2 V to 500.0 V
Maximum recording interval 10 min 10 min, 30 min,
1 h, 2 h, 4 h, 6 h, 12 h, 24 h
Parameter Default Setting Setting Range
Mains signaling voltage measurement
MSV active no
no
yes
No. of MSV frequencies 1 frequency
1 frequency
2 frequencies
Frequency 1 216.60 Hz 100 Hz to 3 kHz
Frequency 2 1060.00 Hz 100 Hz to 3 kHz
Mains signaling voltage capture setting
Detection threshold 1 % of Udin From 1 % to 15 % of Udin
Total recording duration 75 s 15 s to 120 s in 15-s steps
Pretrigger ratio 10 % 0 % to 30 % in 5-% steps
Parameter Default Setting Setting Range
Memory splitting
Event recorder 1.0 % 1 % to 19 %
Measurement recorder 35.0 %
(the recording time depends on
the aggregation interval)
33 % to 51 %
MAN_SICAM_Q100_US.book Page 415 Wednesday, June 5, 2019 9:31 AM

Table of Contents