16 Operating Parameters
16.5 Recording and Reporting
415SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.5.4 Mains Signaling Voltage
16.5.5 Memory Management
Tolerance unit Percentage Percentage
Numerical
Tolerance number Percentage: 3 % of primary
nominal voltage,
Numerical: 0.50 V
1 % to 5 % in 1-% steps
0.2 V to 500.0 V
Maximum recording interval 10 min 10 min, 30 min,
1 h, 2 h, 4 h, 6 h, 12 h, 24 h
Parameter Default Setting Setting Range
Mains signaling voltage measurement
MSV active no
no
yes
No. of MSV frequencies 1 frequency
1 frequency
2 frequencies
Frequency 1 216.60 Hz 100 Hz to 3 kHz
Frequency 2 1060.00 Hz 100 Hz to 3 kHz
Mains signaling voltage capture setting
Detection threshold 1 % of Udin From 1 % to 15 % of Udin
Total recording duration 75 s 15 s to 120 s in 15-s steps
Pretrigger ratio 10 % 0 % to 30 % in 5-% steps
Parameter Default Setting Setting Range
Memory splitting
Event recorder 1.0 % 1 % to 19 %
Measurement recorder 35.0 %
(the recording time depends on
the aggregation interval)
33 % to 51 %
MAN_SICAM_Q100_US.book Page 415 Wednesday, June 5, 2019 9:31 AM