16 Operating Parameters
16.6 Administrative
419SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.6 Administrative
The following administrative settings are available:
• Time synchronization
• Communication Ethernet
• OPC UA PubSub (MQTT)
• Communication serial
• Modbus slave devices 1 to 8
• SICAM subdevices
• Device and language
• Account Management
• Syslog
16.6.1 Time Synchronization
Parameter Default Settings Setting Range
Source time synchronization Internal Internal
Ethernet NTP
Fieldbus
Time zone offset +00:00 -12 to +13 (hours)
(in increments of 0.5 h)
Daylight Saving Time switchover yes no
yes
DST offset +01:00 0 to + 2 (hours)
(in increments of 0.5 h)
Start of DST March
Last week
Sunday
02:00 AM
January to December
First week
Second week
Third week
Fourth week
Last week
Sunday to Saturday
0:00 to 23:00 (full hour)
End of DST October
Last week
Sunday
03:00 AM
January to December
First week
Second week
Third week
Fourth week
Last week
Sunday to Saturday
0:00 to 23:00 (full hour)
Additional Parameters if the Source is Ethernet NTP (Modbus TCP and IEC 61850)
Primary NTP server IP Address 192.168.0.254 Any
Secondary NTP server IP Address 192.168.0.253 Any
No polling of the NTP server if 0.0.0.0
was entered
MAN_SICAM_Q100_US.book Page 419 Wednesday, June 5, 2019 9:31 AM