EasyManua.ls Logo

Siemens SICAM Q100 7KG95 Series - Page 428

Siemens SICAM Q100 7KG95 Series
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 Operating Parameters
16.6 Administrative
428 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Data Format
on Bus
Description Setting Range Invalid
recognition
Used by (example)
Float32
(2 registers)
IEEE Float value -10
38
to +10
38
NaN = invalid
INF = overflow
SENTRON PAC3x00,
SICAM AI 7XV5674,
SICAM T 7KG966,
SICAM P50 7KG775
Int16
(1 register)
16-bit signed
integer
- 32 768 to +32 768 none SENTRON 3WL/3VL
SICAM P50 7KG775
Int16_Ung8000
(1 register)
16-bit signed
integer
-32768 bis +32768 -32768 (8000h)
= ungültig
SIPROTEC 4
UInt16
(1 register)
16-bit integer,
0
0 to +65 535 none SENTRON 3WL/3VL
UInt32
(2 registers)
32-bit integer,
0
0 to +4 294 967 295 none SIPROTEC 4,
SENTRON 3WL/3VL
MAN_SICAM_Q100_US.book Page 428 Wednesday, June 5, 2019 9:31 AM

Table of Contents

Related product manuals