16 Operating Parameters
16.6 Administrative
429SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
16.6.5.3 Mapping – Indications
Parameter Default Setting Setting Range
Name Indication x Slv 1
(x = 1 to 15)
Max. 31 characters
Register type -none- -none-
Coil status registers
Input status registers
Input registers
Holding registers
For -none-, the assignment is ignored
and the corresponding indication cannot
be selected for other functions.
Data format on bus
(See following table.)
1 Bit 1 Bit
1 Bit in UInt32
Data format which is used to transmit the
indication via Modbus
Register number 1 1 to 65 535
Bit offset
(only relevant for register types
Input register or Holding register)
0 0 to 15 (for Data format 1 Bit)
0 to 31 (for Data format 1 Bit in UInt32)
depending on selection for Data format
on bus)
Data Format on Bus Description Setting Range Invalid recognition
1 Bit 1 bit (for all register types; addition-
all select Bit offset for Input regis-
ter and Holding register)
0 = of
1 = on
none
1 Bit in UInt32 1 bit in 2 successive Input registers
or Holding registers which have to
be read together.
0 = of
1 = on
none