4 Measured Quantities and Recording
4.2 Measured Quantities
55SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
4.2.1.6 Measured Quantities of Harmonics Power, Connection Types
Table 4-8 Measurements of Harmonics Power, Connection Types in Power Systems
Measured
Quantity
(x = 1 to 63)
x1 =
Fundamental
Circuit
1-phase
System
3-Wire Network
(Delta)
4-Wire Network
(Star)
Balanced (1I)
Unbalanced (3I)
Unbalanced (2I)
Balanced
(1I)
PQ Values for
ph-N
PQ Values for
ph-ph
Calculate Voltage RMS
values PN & PP = Yes
Calculate Voltage RMS
values PN & PP = No
Calculate Voltage RMS
values PN & PP = Yes
Calculate Voltage RMS
values PN & PP = No
Harmonics Active Power
H_Pa-x a x ---xxx--
H_Pb-x b - ----xx--
H_Pc-x c - ----xx--
SumPa a H_Pa-x---- H_Pa-x - -
SumPb b - ---- H_Pb-x - -
SumPc c - ---- H_Pc-x - -
Harmonics Reactive Power
H_Qa-x a x ---xxx--
H_Qb-x b - ----xx--
H_Qc-x c - ----xx--
SumQa a H_Qa-x - - - - H_Qa-x - -
SumQb b - ---- H_Qb-x - -
SumQc c - ---- H_Qc-x - -
Harmonics Apparent Power
H_Sa-x a x ---xxx--
H_Sb-x b - ----xx--
H_Sc-x c - ----xx--
MAN_SICAM_Q100_US.book Page 55 Wednesday, June 5, 2019 9:31 AM