EasyManua.ls Logo

Siemens SICAM Q100 7KG95 Series - Page 79

Siemens SICAM Q100 7KG95 Series
448 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Measured Quantities and Recording
4.3 Display of Measured Quantities
79SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Harmonics of
voltage H_xV
ph
% or V
10 % to 200 % acc. to
IEC 61000-2-4, class 3
IEC 61000-4-7, class 1:
Condition: V
m
> 1 % V
rated
Maximum error: ±5 % V
m
-------------------------------
Condition: U
m
< 1 % V
rated
Maximum error: ±0.05 % V
rated
Mains signaling voltage
MSV
ph-N
(star) / MSV
ph-
ph
(delta)
V 1 % to 15 % Udin
Condition:
3 % to 15 % of Udin
Maximum error:
±5 % of measured value
-------------------------------
Condition:
1 % to 3 % of Udin
Maximum error:
±0.15 % of Udin
Udin: Primary nominal voltage, corresponds to the primary rated voltage in SICAM Q100
V
m
: Measured value
V
rated
: Rated voltage
u2: Value of Neg.seq.comp.V
u0: Value of Zero seq.comp.V
Table 4-19 Measured Quantities and their Operational Measurement Uncertainty (cont.)
Measured Quantity Unit Measurement Range
Operat. Measurem. Uncertainty acc. to
IEC 62586-1, Class A,
IEC 61000-4-30, IEC 61000-4-7,
and IEC 61000-4-15
MAN_SICAM_Q100_US.book Page 79 Wednesday, June 5, 2019 9:31 AM

Table of Contents

Related product manuals