Communication
2.2 Modbus
29SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
Register 0201 to 0390,
and 6401 to 6484: Measured values (read only), without 0281 to 0292 and 0359 to 0382
Register 0323 to 0358: Flicker (read only)
Register 0392 to 0399: Date/Time for last period PQ calculation (read only)
Register 0401 to 0788,
16001 to 16018
*)
: PQ measured values (read only)
Register 0801 to 0846: Energy counters (read only)
Register 0981 to 0988: Mains signalling voltage evaluation (read only)
Register 1001 to 1378
*)
: Harmonics: voltage values (read only)
Register 1379 to 1756
*)
: Harmonics: current values (read only)
Register 1801 to 2098
*)
: PQ calculation for average harmonic voltage values (read only)
Register 2201 to 2498
*)
: PQ calculation for max. harmonic voltage values (read only)
Register 2601 to 2898
*)
: PQ calculation for average harmonic current values (read only)
Register 2903 to 2980: Tariff counters (read only)
Register 3001 to 3298
*)
: PQ calculation for max. harmonic current values (read only)
Register 3301 to 3756: Tariff values (read only)
Register 4001 to 4378: Phase angles of harmonics: voltage values (read only)
Register 4379 to 4756: Phase angles of harmonics: current values (read only)
Register 5001 to 5099: Last 10 dips (read only)
Register 5201 to 5299: Last 10 swells (read only)
Register 5401 to 5499: Last 10 interrupts (read only)
Register 5501 to 5691: Last 10 RVC Events (read only)
Register 6001 to 6032: Number of PQ events (read only)
Register 6087 to 6100: Load profile – management (read only)
Register 6101 to 6158: Load profile – measured values (read only)
Registers 6485 to 6498: Frequency and voltage deviation (read only)
Registers 6801 to 6804: CO
2
emissions (read only)
Register 7001 to 7378: Prevailing phase angles of harmonics: voltage values (read only)
Register 7379 to 7756: Prevailing phase angles of harmonics: current values (read only)
Register 8001 to 8240: Measured values from Modbus slave devices (read only)
Register 8401 to 8408: Indications from Modbus slave devices (read only)
Register 10001 to 10378: Prevailing ratio of harmonics: voltage values (read only)
Register 10379 to 10756: Prevailing ratio of harmonics: current values (read only)
•Register 12001 to 12378: Phase angle of harmonic power (read only)
•Register 13001 to 13378: Harmonic power - active power value (read only)
SYS_SICAM_Q100_US.book Page 29 Thursday, September 24, 2020 1:17 PM