Communication
2.2 Modbus
82 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2.2.7.55 Registers 30001 to 30032: Measured Values for the Wind Farm Mode (Read
Only)
These registers are only available if you have activated the Wind Farm mode.
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Measured value
Table 2-65 Registers 30001 to 30032: Measured Values for the Wind Farm Mode
Register Type of Information Unit
30001 Firmware version
(string, 4 characters)
-
30003 Frequency Hz
30005 Voltage Avg ph-ph V
30007 Active power W
30009 Reactive power var
30011 U positive sequence V
30013 U negative sequence V
30015 U zero sequence V
30017 I positive sequence A
30019 I negative sequence A
30021 I zero sequence A
30023 Uab RMS V
30025 Ubc RMS V
30027 Uca RMS V
30029 Start of sample period
(number of milliseconds since 1970-01-01 00:00 UTC)
-