Communication
2.2 Modbus
84 SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
For other user port numbers: 3 connection attempts via stan-
dard port 502 and/or 3 connection attempts via user port
Access rights: Default setting: Full
Communication supervision time: Default setting: 60 000 ms
Parameter of Connections
Server port: Server port number of the current connection in the respective
column; if 0 is displayed, the connection is inactive or down
Client IP:Port: Last or current IP address and port number of the client
Received bytes: Total number of bytes received by the TCP port
Sent bytes: Total number of bytes sent to the TCP port
Good messages: Total number of messages received that were detected as valid
Modbus messages
MBAP header errors: Error in the MBAP header: incorrect protocol ID or implausible
length of data
Exception responses: Counters of the transmitted exception response messages
Access rights violations: Total number of write accesses received if the parameter Access
rights for port xxx is set to Read only of the associated TCP
port (for example 502) in the Communication Ethernet input/
output window. For more information, see the device manual,
chapter 8 - Ethernet Communication)
2.2.8.2 Modbus RTU Slave Diagnosis
Figure 2-7 Modbus RTU Slave Diagnosis
Parameter
The following parameters are displayed with Modbus RTU Slave:
Device address: Default setting: 1
Baud rate: Default setting: 19 200 bit/s
Parity: Default setting: Even
Access rights: Default setting: Full
Communication supervision time: Default setting: 60 000 ms