EasyManua.ls Logo

Siemens SICAM Q100 - Page 105

Siemens SICAM Q100
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Connection Principle
7.1 Terminals
105SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Functions of the Terminals at SICAM Q100
Table 7-2 Functions of the Terminals
Terminal Assigned Function,
Measured Value or
Indication
Description
E: I
A
L1
=>
Ia Conductor a, input, current measurement
E: I
A
L1
<=
Ia Conductor a, output, current measurement
E: I
B
L2
=>
Ib Conductor b, input, current measurement
E: I
B
L2
<=
Ib Conductor b, output, current measurement
E: I
C
L3
=>
Ic Conductor c, input, current measurement
E: I
C
L3
<=
Ic Conductor c, output, current measurement
E: I
N
=>
N Neutral conductor, input current measurement
E: I
N
<=
N Neutral conductor, output, current measurement
F:
A
L1
Van Conductor a, voltage measurement
F:
B
L2
Vbn Conductor b, voltage measurement
F:
C
L3
Vcn Conductor c, voltage measurement
F: N N Neutral conductor, voltage measurement
G: 1 Binary output 1 Binary output 1
G: 2 Root Common root for both binary outputs
G: 3 Binary output 2 Binary output 2
H: Protective conductor -
H: N / - N/- Neutral conductor of the mains voltage or
negative supply voltage
H: L / + ph/+ Phase of the mains voltage or
positive supply voltage
U: 1 Binary input 1 Binary input 1
U: 2 Root Common root for both binary inputs
U: 3 Binary input 2 Binary input 2

Table of Contents

Other manuals for Siemens SICAM Q100

Related product manuals