EasyManua.ls Logo

Siemens SICAM Q100 - Page 110

Siemens SICAM Q100
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Connection Principle
7.3 Connection Types and Connection Examples
110 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Example 3-wire Network, 2 Voltage Transformers and 2 Current Transformers, Unbalanced
Figure 7-8 Example 3-wire Network, 2 Voltage Transformers and 2 Current Transformers, Unbalanced
a
b
P1 P2
S1 S2
c
AAB
B
aabb
P1
P2
S1 S2
PE
10 A 10 A10 A
Terminals SICAM Q100
NOTICE
The secondary voltage on terminal F (voltage) must not exceed AC 600 V (AC 347 V for UL).
Non-observance can cause material damage.
Make sure that the maximum permissible phase-to-ground voltage (PE) is not exceeded.

Table of Contents

Other manuals for Siemens SICAM Q100

Related product manuals