8 Operation at Use of a PC
8.3 Configuration of the Device
130 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3 Configuration of the Device
8.3.1 Device Configuration Procedure
If you have not changed the set of parameters since the first start of the device (see chapter 8.2.1), use the
factory settings (see chapter 8.3.3 to chapter 8.3.7). To change the settings of the set of parameters, proceed
as follows:
Click the Configure tab on the user interface.
Figure 8-15 Configure Tab
Select the Prepare menu in the navigation window and then either Get device configuration or Open
configuration from file.
NOTE
The device contains two sets of parameters. The set of parameters currently used for device operations is the
active set of parameters. The inactive set of parameters is called the passive set of parameters.
The following sections describe how to change and enable the passive set of parameters.