8 Operation at Use of a PC
8.3 Configuration of the Device
146 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.3.1.3 Binary Outputs G1/G2 and G3/G2
Default Settings and Setting Ranges of the Binary Outputs G1/G2 and G3/G2
Table 8-4 Settings of Binary Outputs G1/G2 and G3/G2
Parameter Default Setting Setting Range
Source type Indication Indication
Energy counter
Source Type Indication
Indication -none- Acc. to list box
(see chapter 15)
Source inverted no no
yes
Operating mode Persistent Persistent
Persistent with fail safe
Pulse
Pulse with retrigger
Output time for pulse operating mode
(setting only possible if operating
modes Pulse and Pulse with retrig-
ger)
20 (* 10 ms) 50 ms to 3 600 000 ms
Source Type Energy Counter
Energy counter -none- Acc. to list box
(see chapter 15)
Energy increase per pulse 1.0 Wh 0.1 Wh/VAh/varh to 1 000 000 Wh/VAh/
varh
Output time for pulse operating mode 20 (* 10 ms) 50 ms to 3 600 000 ms