EasyManua.ls Logo

Siemens SICAM Q100 - Page 168

Siemens SICAM Q100
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Operation at Use of a PC
8.3 Configuration of the Device
168 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.6.2 Trigger Management
Default Settings and Setting Ranges
Table 8-13 Trigger Management
Parameter Default Setting Setting Range
Voltage trigger limits
Trigger active no no
yes
Tolerance unit Percentage Percentage
Numerical
Lower threshold 90.00 % of the
nominal/declared
supply voltage
0.00 % to 99.99 % of the nominal/declared supply
voltage
0.0 V to 1 000 000.0 V
Upper threshold 110.00 % of the
nominal/declared
supply voltage
100.0 % to 10 000.0 % of the nominal/declared supply
voltage
0.0 V to 1 000 000.0 V
Hysteresis 2.00 % of the nominal/
declared supply
voltage
0.0 % to 50.0 % of the nominal/declared supply
voltage
Detection mode
1)
ph-N ph-N
ph-ph
Current trigger limits
Trigger active no no
yes
Tolerance unit Percentage Percentage
Numerical
Lower threshold 90.00 %
of nominal current In
0.00 % to 99.99 % of of nominal current In
0.0 A to 1 000 000.0 A
Upper threshold 110.00 %
of nominal current In
100.0 % to 10 000.0 % of of nominal current In
0.0 A to 1 000 000 A
Hysteresis 2.00 %
of nominal current In
0.0 % to 50.0 % of of nominal current In
Configuration binary trigger
Trigger active no no
yes
Trigger source Binary Input 1 Indication 1 from Remote
Indication 2 from Remote
Binary Input 1
Binary Input 2
Trigger value OFF ON
OFF
Waveform capture setting

Table of Contents

Other manuals for Siemens SICAM Q100

Related product manuals