8 Operation at Use of a PC
8.3 Configuration of the Device
168 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.6.2 Trigger Management
Default Settings and Setting Ranges
Table 8-13 Trigger Management
Parameter Default Setting Setting Range
Voltage trigger limits
Trigger active no no
yes
Tolerance unit Percentage Percentage
Numerical
Lower threshold 90.00 % of the
nominal/declared
supply voltage
0.00 % to 99.99 % of the nominal/declared supply
voltage
0.0 V to 1 000 000.0 V
Upper threshold 110.00 % of the
nominal/declared
supply voltage
100.0 % to 10 000.0 % of the nominal/declared supply
voltage
0.0 V to 1 000 000.0 V
Hysteresis 2.00 % of the nominal/
declared supply
voltage
0.0 % to 50.0 % of the nominal/declared supply
voltage
Detection mode
1)
ph-N ph-N
ph-ph
Current trigger limits
Trigger active no no
yes
Tolerance unit Percentage Percentage
Numerical
Lower threshold 90.00 %
of nominal current In
0.00 % to 99.99 % of of nominal current In
0.0 A to 1 000 000.0 A
Upper threshold 110.00 %
of nominal current In
100.0 % to 10 000.0 % of of nominal current In
0.0 A to 1 000 000 A
Hysteresis 2.00 %
of nominal current In
0.0 % to 50.0 % of of nominal current In
Configuration binary trigger
Trigger active no no
yes
Trigger source Binary Input 1 Indication 1 from Remote
Indication 2 from Remote
Binary Input 1
Binary Input 2
Trigger value OFF ON
OFF
Waveform capture setting