8 Operation at Use of a PC
8.3 Configuration of the Device
170 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.6.3 Recorder Parameter
Default Settings and Setting Ranges
1)
The interval of aggregated values of harmonics and interharmonics will always synchronize with the setting
of Average interval in Measurement recorder.
Table 8-14 Recorder Parameter
Parameter Default Setting Setting Range
Measurement Recorder
Average intervals - Frequency 10 s fixed
Short term flicker 10 min fixed
Long term flicker 2 h fixed
Average interval - Voltage,
Unbalance and Harmonics
10 min 30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
Record additional data (I, P, Q,
S etc.)
no no
yes
Recorder of average - Min no no
yes
Recorder of average - Max no no
yes
Harmonics parity Odd Even
Odd
All
File generation every:
1)
(corresponds to the setting of
the Average interval parame-
ter)
The created PQDIF files can be
downloaded via the user inter-
face or with the IEC 61850 pro-
tocol.
24 h At average interval File generation
every:
30 s 1 h (fix)
1 min 2 h (fix)
10 min, 15 min,
30 min, 1 h or
2 h
2 h
4 h
6 h
12 h
24 h
Recorded file type PQDIF PQDIF (see chapter 8.4.2.5)
CSV
All
Flicker lamp model 230 V 230 V
120 V
Trend Recorder
Tolerance unit Percentage Percentage
Numerical
Tolerance number Percentage: 3 % of primary
nominal voltage,
Numerical: 0.5 V
1% to 5% in 1-% steps
0.2 V to 500.0 V
Maximum recording interval 10 min 10 min, 30 min,
1 h, 2 h, 4 h, 6 h, 12 h, 24 h