8 Operation at Use of a PC
8.3 Configuration of the Device
175SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.6.4 Mains Signalling Voltage
Default Settings and Setting Ranges
Changing the Mains Signalling Voltage Parameters
To change the Mains signalling voltage, proceed as follows:
In the navigation window, select the Recording and Reporting menu and click Mains signalling
voltage.
Table 8-16 Mains Signalling Voltage
Parameter Default Setting Setting Range
Mains signalling voltage measurement
MSV active no no
yes
No. of MSV frequencies 1 frequency 1 frequency
2 frequencies
Frequency 1 216.60 Hz 100 Hz to 3 kHz
Frequency 2 1060.00 Hz 100 Hz to 3 kHz
Mains signalling voltage capture setting
Detection threshold 1 [% of Udin] 1 % to 15 % of Udin
Total recording duration 75 s 15 s to 120 s in 15-s steps
Pretrigger ratio 10 % 0 % to 30 % in 5-% steps