8 Operation at Use of a PC
8.3 Configuration of the Device
179SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.6.6 Report Configuration
The Report configuration allows you to parameterize the PQ threshold parameters (User defined). You can
adjust the process connections to the installation environment and enter different operational settings.
Alternatively, you can use the default values according to EN 50160 LV&MV or EN 50160 HV.
Default Settings and Setting Ranges
Table 8-18 Report Configuration
Parameter Default Setting Setting Range
General Information
Company:
Department:
Supervisor:
Inspector:
Location:
Comment:
- Any text displayed in the
printout of the power quality
report
Power Quality Report
Evaluation mode according to: EN 50160 LV&MV EN 50160 LV&MV
EN 50160 HV
User defined
Flagging acc. to
IEC 61000-4-30
no no
yes
Power frequency
99.5 % of measurement should be in -1.0 % to 1.0 % deviation of the
power frequency.
100 % of measurement should be in -6.0 % to 4.0 % deviation of the
power frequency.
Any setting for user-defined
evaluation mode
Power supply voltage magnitude
95 % of measurement should be in -10.0 % to 10.0 % deviation of the
nominal/declared supply voltage.
100 % of measurement should be in -15.0 % to 10.0 % deviation of
the nominal/declared supply voltage.
Any setting for user-defined
evaluation mode
Flicker severity
95 % of measurement should be less than 1.0
Voltage unbalance
1)
95 % of measurement should be less than 2.0 %.
100 % of measurement should be less than 3.0 %.
Any setting for user-defined
evaluation mode
Subgroup Total Harmonic Distortion factor (THDS)
95 % of measurement should be less than 8.0 %.
Any setting in % for user-
defined evaluation mode