8 Operation at Use of a PC
8.3 Configuration of the Device
180 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
1)
According to EN 50160, up to 3 % unbalance can occur in 3-wire networks in areas with many 1-wire and
2-wire connections.
2)
The frequency “YYY” and limit “xxx” are based on the configured frequency.
Voltage event interruptions
1. Short interruption until 1 second duration
2. Short interruption until 3 minute duration
3. Long interruption longer than 3 minute duration
Any setting for user-defined
evaluation mode
Harmonic voltages
Even harmonics
Odd harmonics: multiples of 3
Odd harmonics: not multiples of 3
Any setting for user-defined
evaluation mode
Mains signalling voltages
2)
Supply voltage should be in -15.0 % to +15.0 % deviation of the
nominal/declared supply voltage
99.0 % of “YYY” Hz mains signalling voltage should be less than “xxx”
% of the nominal/declared supply voltage
Any setting for user-defined
evaluation mode
Table 8-18 Report Configuration (cont.)
NOTE
The factory settings are based on EN 50160. If you have changed the settings, the set parameters are applied
after a device restart. Resetting to the factory settings is possible.