8 Operation at Use of a PC
8.3 Configuration of the Device
184 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.6.8 Transient Detection
Default Settings and Setting Ranges
Parameterizing the Transient Detection
If you want to change the Transient reference level, proceed as follows:
In the navigation window of the Recording and Reporting menu, click the element Transient reference
level.
Figure 8-52 Configure tab, transient reference level input/output window
Change the parameter according to Table 8-16.
After the parameterization click Send.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
If you do not want to make any additional settings, continue with the Activation of the device configuration
according to section Activating the Set of Parameters. If you want to change other settings, enter the
changes and then enable the device configuration as described in section Activating the Set of
Parameters.
Table 8-20 Transient Detection
Parameter Default Setting Setting Range
Transient reference level 110 % 110 % to 240 % of the nominal/declared supply
voltage