8 Operation at Use of a PC
8.3 Configuration of the Device
185SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.7 Setting Administrative Parameters
In the Configure tab you can view and if necessary edit the administrative settings. You can select the
parameters in the Administrative menu in the navigation window. These parameters can be changed in the
input/output windows:
• Time synchronization
• Communication Ethernet
• Communication serial
• Modbus slave devices 1 to 8 (only if the Modbus RTU Master protocol has been selected)
• SICAM subdevices
• Device and language
8.3.7.1 Time Synchronization
Default Settings and Setting Ranges of the Time Synchronization
NOTE
Observe the procedure for the device configuration described in chapter 8.3.1 when setting the administrative
parameters.
Table 8-21 Time Synchronization Settings
Parameter Default Setting Setting Range
Source time synchronization Internal Acc. to list box
(see chapter 15)
Time zone offset to UTC +00:00 -12 to +13 (hours)
(in increments of 0.5 h)
Daylight Saving Time switchover yes no
yes
DST offset +01:00 0 to + 2 (hours)
(in increments of 0.5 h)
Start of DST March
Last week
Sunday
02:00 AM
Acc. to list boxes
(see chapter 15)
End of DST October
Last week
Sunday
03:00 AM
Acc. to list boxes
(see chapter 15)
Additional Parameters if the Source is Ethernet NTP (Modbus TCP and IEC 61850)
Primary NTP server IP address 192.168.0.254 Any
Secondary NTP server IP address 192.168.0.253 Any
No polling of the NTP server if
0.0.0.0 was entered