8 Operation at Use of a PC
8.3 Configuration of the Device
187SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.3.7.2 Communication Ethernet
Default Settings and Setting Ranges of the Communication Ethernet
Table 8-22 Communication Ethernet Settings
Parameter Default Setting Setting Range
Communication Ethernet
IP address
1)
192.168.0.55 Any
0.0.0.0 = DHCP
Subnet mask
1)
255.255.255.0 Any
Default gateway
1)
192.168.0.1 Any
Ethernet switch on no no
yes
Enable SNMP no no
yes
Bus protocol Modbus TCP -none-
Modbus TCP
IEC 61850
Both
Protocol Modbus TCP
Use a user-port number
2)
no no
yes
User-port number
2)
(can only be set when Use a user-port
number is parameterized with yes)
10 000 10 000 to 65 535
Access rights for user port
(can only be set when Use a user-port
number is parameterized with yes)
Full Full
Read only
Access rights for port 502 Full Full
Read only
Keep Alive time 10 s 0 s = switch off
1 s to 65 535 s
Communication supervision time 600 (* 100 ms) 0 s = none
100 ms to 6 553 400 ms
Modbus TCP/RTU Gateway
(Condition: The Modbus RTU Master protocol must have been selected under serial communication.)
Activated no no
yes