EasyManua.ls Logo

Siemens SICAM Q100 - Page 188

Siemens SICAM Q100
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Operation at Use of a PC
8.3 Configuration of the Device
188 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
1)
After the parameter changes have been enabled, the device will reset.
2)
After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later reopen these connections.
3)
These values are necessary if no Modbus slave device has been configured for the requested Unit ID. If a
Modbus slave device was configured, its values are used.
Unit ID of this device 255 1 to 255
Retry limit
3)
2 0 to 10
Response timeout
3)
10 (* 10 ms) (1 to 6000) * 10 ms
= 10 ms to 60 s
Protocol IEC 61850
IED Name SICAM_Q100_01 Max. 60 characters
Only a to z, A to Z, _, 0 to 9
are permitted.
The first character must be a
letter.
Voltage - Dead band 5 % 1 % to 5 %, in 1-% steps
Current - Dead band 5 % 1 % to 5 %, in 1-% steps
Power - Dead band 5 % 1 % to 5 %, in 1-% steps
Power factor - Dead band 5 % 2 % to 5 %, in 1-% steps
Frequency - Dead band 0.05 % 0.02 %
0.05 %
Table 8-22 Communication Ethernet Settings (cont.)
Parameter Default Setting Setting Range

Table of Contents

Other manuals for Siemens SICAM Q100

Related product manuals