EasyManua.ls Logo

Siemens SICAM Q100 - Page 208

Siemens SICAM Q100
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Operation at Use of a PC
8.3 Configuration of the Device
208 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Description and setting ranges of the parameters in the text file:
Table 8-29 Description and setting ranges of the parameters in the text file.
Label Measured
Quantity (MV)
Indication (I)
Description Setting Range
MT MV Mapping Type
(Data type)
MEASURAND
INDICATION
DS MV, I Description
Name of the associated data object
String with max. 31 characters
Longer strings are cut at 31 charac-
ters during import.
RN MV, I Register number
(within the selected register type
RT)
1 to 65 535
RT MV, I Register type 0x0 – Coil status register
0x1 – Input status register
0x3 – Input register
0x4 – Holding register
OF I Bit offset
(for INDICATION in Holding regi-
sters)
0 to 15 (for FT = 1BIT)
0 to 31 (for FM = 1BITINUINT32)
FM MV, I Data format For MEASURAND:
FLT32, INT16, UINT16, UINT32,
INT16INV7FFF and INT16INV8000
For INDICATION:
1BIT, 1BITINUINT32
SC MV Scaling factor for MEASURAND Arbitrary float value
UN MV Unit-multiplier for MEASURAND 1: dimensionless
2: Meter
3: kg
4: s
5: A
23: °C
29: V
33: Hz
38: W
39: Pa
41: m
2
42: m
3
61: VA
63: var
64: °
71: VAh
72: Wh
73: varh
75: %
76: °F

Table of Contents

Other manuals for Siemens SICAM Q100

Related product manuals