8 Operation at Use of a PC
8.3 Configuration of the Device
208 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Description and setting ranges of the parameters in the text file:
Table 8-29 Description and setting ranges of the parameters in the text file.
Label Measured
Quantity (MV)
Indication (I)
Description Setting Range
MT MV Mapping Type
(Data type)
MEASURAND
INDICATION
DS MV, I Description
Name of the associated data object
String with max. 31 characters
Longer strings are cut at 31 charac-
ters during import.
RN MV, I Register number
(within the selected register type
RT)
1 to 65 535
RT MV, I Register type 0x0 – Coil status register
0x1 – Input status register
0x3 – Input register
0x4 – Holding register
OF I Bit offset
(for INDICATION in Holding regi-
sters)
0 to 15 (for FT = 1BIT)
0 to 31 (for FM = 1BITINUINT32)
FM MV, I Data format For MEASURAND:
FLT32, INT16, UINT16, UINT32,
INT16INV7FFF and INT16INV8000
For INDICATION:
1BIT, 1BITINUINT32
SC MV Scaling factor for MEASURAND Arbitrary float value
UN MV Unit-multiplier for MEASURAND 1: dimensionless
2: Meter
3: kg
4: s
5: A
23: °C
29: V
33: Hz
38: W
39: Pa
41: m
2
42: m
3
61: VA
63: var
64: °
71: VAh
72: Wh
73: varh
75: %
76: °F