EasyManua.ls Logo

Siemens SICAM Q100 - Page 211

Siemens SICAM Q100
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Operation at Use of a PC
8.3 Configuration of the Device
211SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Server IP address 192.168.0.57 any
(different from IP address of subde-
vice 1 and in the same subnet as
SICAM Q100)
Server port 51 000 10 000 to 65 535
Response timeout 3 (* 10 ms) 10 ms to 60 000 ms
0 ms = invalid
Parameter: Source of output 1-N
Indication: Input 1-N
Indication 9 from Remote
Binary inp. 1-N SICAM IO 2
Parameter: see chapter 15
Indication: any, max. 31 characters
Parameter Source of output:
Selection which indication is trans-
mitted from SICAM Q100 to the
binary output of the SICAM I/O Unit
7XV5673.
Indication Input:
Designation of the indication which
shows the status of the binary input
of SICAM I/O Unit 7XV5673.
Parameter: Source of output 2-N
Indication: Input 2-N
Indication 10 from Remote
Binary inp. 2-N SICAM IO 2
Parameter: Source of output 3-N
Indication: Input 3-N
Indication 11 from Remote
Binary inp. 3-N SICAM IO 2
Parameter: Source of output 1-P
Indication: Input 1-P
Indication 12 from Remote
Binary inp. 1-P SICAM IO 2
Parameter: Source of output 2-P
Indication: Input 2-P
Indication 13 from Remote
Binary inp. 2-P SICAM IO 2
Parameter: Source of output 3-P
Indication: Input 3-P
Indication 14 from Remote
Binary inp. 3-P SICAM IO 2
Table 8-30 Settings of the SICAM Subdevices (cont.)
Parameter/Indications Default Setting Setting Range

Table of Contents

Other manuals for Siemens SICAM Q100

Related product manuals