8 Operation at Use of a PC
8.3 Configuration of the Device
213SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
The factory settings of the Source of output x parameters are controllable indications, for example,
Indication 3 from Remote, and can be controlled via the Modbus TCP or IEC 61850 protocols. You can also
parameterize an internal indication from SICAM Q100 in the list boxes.
If one or two SICAM I/O Units have been selected as subdevices, the indications on the status of the binary
inputs of these devices are also available in the group indications (see chapter 8.3.3.2.2), the indications of the
LEDs (see chapter 8.3.3.1.4), and the indications of the binary outputs (chapter 8.3.3.1.3).
8.3.7.5.2 Parameter Settings of the SICAM I/O Unit 7XV5673 (Subdevice)
Settings of the Ethernet Communication of the SICAM I/O Unit
NOTE
A detailed description of all parameter settings of the SICAM I/O Unit 7XV5673 and a description of that device
is given in the Device Manual, order number E50417-H1040-C484.
Table 8-31 Settings of the Ethernet Communication in the SICAM I/O Unit Subdevice
Parameter Default Setting Setting Range
IP address At IP address, enter the same IP address as in SICAM Q100 I/O Unit sub-
device under Server IP address.
SICAM Q100 and SICAM I/O Unit must have different IP addresses.
Subnet mask 255.255.255.0 Identical to the subnet mask of the SICAM Q100
Default gateway 192.168.0.1 Any
Ethernet switch on no Activation of the second port of the internal Ether-
net switch
Bus protocol/Operating
mode
I/O Mirror server You must select I/O Mirror Server for connection to
the SICAM Q100.
Operating Mode I/O Mirror Server
Port number 51 000 Port number for the Ethernet communication
between SICAM Q100 and SICAM I/O Unit
Communication super-
vision time
8 (*10 ms) –