8 Operation at Use of a PC
8.4 Value View and Evaluation
242 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.4.2.5 File Transfer
You can download the data from the SICAM Q100 in the standard format.
Trend records: PQDIF files
Measurements: PQDIF files and CSV files
Records for fault recorder: COMTRADE files
MSV recorder: COMTRADE files
Default Settings and Setting Ranges
1)
Observe the information on how to download multiple files given in this chapter.
Table 8-40 File Transfer
Parameter Default Setting Setting Range
Start date Current date Any
Calendar function
Time format: YYYY-MM-DD
End date Current date Any
Calendar function
Time format: YYYY-MM-DD
Recorder type Trend recorder (PQDIF) Trend recorder (PQDIF)
Measurement recorder (PQDIF)
Measurement recorder (CSV)
Fault recorder (COMTRADE)
MSV recorder (COMTRADE)
Download type Single file download Single file download
Multiple file download
1)
Recorder list -none- A file is generated as recording list in the
corresponding data format depending on the
parameterized data type and recorder type.