8 Operation at Use of a PC
8.5 Maintenance
255SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.5.3.3 Min/Max Values
To reset the min/max values, proceed as follows:
In the navigation window, select the Presets menu and click Min/Max Values.
Figure 8-103 Maintenance Tab, Preset Min/Max Values
Enter the maintenance password into the Password field.
Click Reset Min/Max Values.
All min/max values are reset. The Action was successful indication is displayed on the status bar.
8.5.3.4 Load Profile
To reset the load profile, proceed as follows:
In the navigation window, select the Presets menu and click Load profle.
Figure 8-104 Maintenance Tab, Preset Load Profile