8 Operation at Use of a PC
8.5 Maintenance
259SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.5.4.3 Audit Log
The device provides an audit log to track the security-relevant events. A dedicated password is required to view
the audit log. Only a user with the auditor rights can access it.
The Audit log is located in the Maintenance tab. To view the Audit log, proceed as follows:
In the navigation window, select the Message logs menu and click Audit log.
Figure 8-108 Maintenance Tab, Access Audit Log
Enter the audit log password into the Password field.
Click Display.
Audit messages are displayed on the HTML pages.
Figure 8-109 Maintenance Tab, Display Audit Log
To refresh the display of the audit log, click Audit log or press F5, and enter the audit log password again.
NOTE
The audit log is only available via HTML pages, not via the device display.
The audit log stores the latest 2048 audit messages. The older messages are automatically overwritten.
You cannot delete the audit messages manually.
For a new delivered device, audit logs created during production process are kept.