8 Operation at Use of a PC
8.7 Example of a Parameterization and Measured Value Evaluation
267SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
8.7 Example of a Parameterization and Measured Value Evaluation
8.7.1 Task Definition
✧ Set the parameters via the Ethernet interface using the default IP address set upon delivery of the device.
✧ Configure SICAM Q100 according to the topology.
✧ Parameterize the indication of a imit violation for V
ab
> 11 kV with 10 % hysteresis and name the indication.
✧ Parameterize a binary output that is switched on for the duration of the limit violation.
✧ Communicate via serial communication using device address 1, with a baud rate of 19.2 kbit/s, even
parity, full access rights, and a monitoring time of 1 min.
✧ Parameterize the Ethernet communication according to the network configuration specified by the system
operator.
✧ Assign any name and specify the time/date format as YYYY-MM-DD and the time in 24-hour format.
✧ Parameterize the Measurement recorder with an averaging time of 2 hours and activate the averaging
recorders for minimum and maximum values. Record all voltage harmonics.
✧ Allocate 50 % storage capacity to the Measurement recorder.
✧ Take over the factory-set report configuration.
✧ Activate the device configuration you have created as the active parameter set.
✧ Perform measurements, acquire the limiting value indication and record the measured values as defined
in the task.
8.7.2 Initial Situation
Topology
• 4-wire system
• Rated input voltage (ph-ph): AC 10 kV
• Rated input current: AC 100 A
• Rated frequency: 50 Hz
• Connection: any load via transformers
• Voltage transformer: 10 000 V : 100 V
• Current transformer: 100 A : 1 A
• Primary nominal voltage: 230.00 V
• Communication via Ethernet and RS485 interfaces
Network Configuration
• Default IP address: 192.168.0.55
• User IP address: 192.168.1.40 (customer-specific)
• Subnet mask: 255.255.255.0
• Default gateway: 192.168.1.1