8 Operation at Use of a PC
8.7 Example of a Parameterization and Measured Value Evaluation
273SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
✧ On the Configure tab, Memory management menu item (see chapter 8.4.2.6) allocate 50 % of the
storage capacity to the Measurement recorder and activate the ring buffer function.
Figure 8-123 Configure Tab, Memory Management Example
✧ Confirm the factory-set report configuration (see chapter 8.3.6.6).
✧ On the Configure tab, Recording control menu item (see chapter 8.3.6.7) select Start immediately.
Figure 8-124 Configure Tab, Start Immediately Example
✧ Go to the Configure tab, Save configuration to file menu item to save your device configuration as the
active parameter set as described in Save Configuration to File.