8 Operation at Use of a PC
8.7 Example of a Parameterization and Measured Value Evaluation
273SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
On the Configure tab, Memory management menu item (see chapter 8.4.2.6) allocate 50 % of the
storage capacity to the Measurement recorder and activate the ring buffer function.
Figure 8-123 Configure Tab, Memory Management Example
Confirm the factory-set report configuration (see chapter 8.3.6.6).
On the Configure tab, Recording control menu item (see chapter 8.3.6.7) select Start immediately.
Figure 8-124 Configure Tab, Start Immediately Example
Go to the Configure tab, Save configuration to file menu item to save your device configuration as the
active parameter set as described in Save Configuration to File.