9 Operation at Use of the Display
9.4 Parameterization
289SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
1)
Separate CT In is available only if the following Connection type is selected: 3P4W (four-wire, any load).
Table 9-3 Basic Parameter Settings
Parameter Default Setting Setting Range
Voltage Inputs
Connection type 3P4W 1P2W (1-phase system)
3P3WB (three-wire, equal load)
3P3W_2I (three-wire, any load (2*I))
3P3W_3I (three-wire, any load (3*I))
3P4WB (four-wire, equal load)
3P4W (four-wire, any load)
Use PTs? No (no checkmark) Yes (checkmark)
No (no checkmark)
Use PTs:
PT primary
PT secondary
AC 10 000 V
AC 100 V
AC 100 V to 1 000,000 V
AC 1 V to 460 V
Primary nominal voltage
(Phase-N/PE)
230.00 V AC 57.73 V to 400 V (autorange)
IEC 61000-4-30 Class A: to AC 230 V:
200 % overvoltage
> AC 230 V to 400 V: 200 % to 15 %
overvoltage
UL conditions:
to AC 170 V: 200 % overvoltage
> AC 170 V to 300 V: 200 % to 15 %
overvoltage
Current Inputs
Use CTs? No (no checkmark) Yes (checkmark)
No (no checkmark)
Use CTs:
CT primary
CT secondary
Separate CT In
1)
?
AC 1 000.00 A
AC 1.00 A
No (no checkmark)
AC 1.0 A to 100 000.0 A
AC 1.0 A to 10.00 A
Yes (checkmark)
No (no checkmark)
Separate CT In?
CT Primary In AC 1 000.00 A AC 1.0 A to 100 000.0 A
Zero-Point Suppression
Zero-point suppression
(in % of Vrated
and Irated)
0.3 % 0.0 % to 10.0 %