13 Technical Data
13.2 Test Data
327SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
13.2 Test Data
Reference Conditions according to IEC 62586-1 for Determining the Test Data
13.2.1 Electrical Tests
Standards
Insulation Test according to IEC EN 61010-1 and IEC EN 61010-2-030
Ambient temperature 23 °C ± 2 °C
Relative humidity 40 % to 60 % RH
Supply voltage V
PS
± 1 %
Phases (3-wire network) 3
External continuous magnetic fields DC field: 40 A/m
AC field: 3 A/m
DC components V/I none
Signal waveform sinus
Frequency 50 Hz ± 0.5 Hz
60 Hz ± 0.5 Hz
Voltage magnitude Udin ± 1 %
Flicker Pst < 0.1 %
Unbalance (all channels) 100 % ± 0.5 % of Udin
Harmonic 0 % to 3 % of Udin
Interharmonic 0 % to 0.5 % of Udin
Standards: IEC EN 61000-6-2
IEC EN 61000-6-4
IEC EN 61010-1
IEC EN 61010-2-030
Inputs/Outputs Insulation Rated
Voltage
ISO Test Voltage Category
Current measurement inputs Reinforced 150 V AC 2.3 kV Cat. III
Voltage measurement inputs Reinforced 600 V Surge voltage
9.76 kV
Cat. III
300 V Cat. IV
Supply voltage Reinforced 300 V DC 3.125 kV Cat. III
Binary outputs Reinforced 300 V AC 3.536 kV Cat. III
Binary inputs Reinforced 300 V AC 3.536 kV Cat. III
Ethernet interface SELV < 24 V AC 1500 V -
RS485 interface SELV < 24 V DC 700 V -