EasyManua.ls Logo

Siemens SICAM Q100 - Binary Inputs U1;U2 and U3;U2

Siemens SICAM Q100
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15 Operating Parameters
15.1 Process Connections
339SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
1)
Power quality values for and Calculate Voltage RMS values PN and PP are available only under Net-
work type is selected as Four-wire, three phase, unbalanced.
2)
Transformer ratio In is available only if the following Network type is selected: Four-wire, three phase,
unbalanced.
15.1.2 Binary Inputs U1/U2 and U3/U2
Parameter Default Settings Setting Range
Threshold voltage
Threshold voltage
(one setting for both binary inputs)
19 V 19 V
88 V
176 V
Binary inputs
Terminals U1/2
Routed as:
1)
Status information Status information
Load profile source
Tar iff s our ce
Software filter time
(only settable if Routed as: Status information
has been set)
1 (* 2 ms) 2 ms to 120 000 ms
(settable in 2-ms increments)
Source inverted no no
yes
Add entry to operational log
(only settable if Routed as: Status information
has been set)
yes no
yes
Binary input indication Binary Input 1 Any
Max. 31 characters
2)
Terminals U3/2
Routed as:
1)
Status information Status information
Load profile source
Tar iff s our ce
Software filter time
(only settable if Routed as: Status information
has been set)
1 (* 2 ms) 2 ms to 120 000 ms
(settable in 2-ms increments)
Source inverted no no
yes
Add entry to operational log
(only settable if Routed as: Status information
has been set)
yes no
yes
Binary input indication Binary Input 2 Any
Max. 31 characters
2)

Table of Contents

Other manuals for Siemens SICAM Q100

Related product manuals