EasyManua.ls Logo

Siemens SICAM Q100 - Limit Violation 1-8 and 9-16

Siemens SICAM Q100
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15 Operating Parameters
15.2 Automation Functions
345SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
15.2.1 Limit Violation 1-8 and 9-16
1)
31 bytes of UTF-8
Parameter Default Setting Setting Range
Measurement -none- -none-
Va, Vb, Vc
Vab, Vbc, Vca
Ia, Ib, Ic
VN, Vavg
IN, Iavg
Pa, Pb, Pc, P
Qa, Qb, Qc, Q
Sa, Sb, Sc, S
cos (a), cos (b), cos (c), cos
PFa, PFb, PFc, PF
UIa, UIb, UIc, UI
f
Neg.seq.comp.V
Neg.seq.comp.I
THDS Va, THDS Vb, THDS Vc
THDS Vab, THDS Vbc, THDS Vca
THDS Ia, THDS Ib, THDS Ic
ab V, bc V, ca V
ab I, bc I, ca I
Q1a, Q1b, Q1c; Q1
Pinst (a-n), Pinst (b-n),Pinst (c-n)
Pst (a-n), Pst (b-n),Pst (c-n)
Plt (a-n), Plt (b-n),Plt (c-n)
Pinst (a-b), Pinst (b-c), Pinst (c-a)
Pst (a-b), Pst (b-c), Pst (c-a)
Plt (a-b), Plt (b-c), Plt (c-a)
Zero seq.comp.V
Zero seq.comp.I
MV x from Bus device y
*)
(x = 1 to 15 and y = 1 to 8)
(Setting ranges pending from network type)
*)
Designation can be changed during the
parameterization.
Limit 0.00 -1 000 000 000 to 1 000 000 000 (unit)
Limit type Lower Lower
Upper
Hysteresis (%) 1.0 0.0 to 10.0
Violation indication Limit Violation x
(x = 1 to 16)
Any
Max. 31 characters
1)

Table of Contents

Other manuals for Siemens SICAM Q100

Related product manuals