15 Operating Parameters
15.5 Recording and Reporting
352 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
15.5.2 Trigger Management
1)
The detection mode will always synchronize with the setting of Record ph-ph voltage.
Parameter Default Setting Setting Range
Voltage trigger limits
Trigger active no no
yes
Tolerance unit Percentage Percentage
Numerical
Lower threshold 90.00 %
of the nominal/declared
supply voltage
0.00 % to 99.99 % of the nominal/declared
supply voltage
0.0 V to 1 000 000.0 V
Upper threshold 110.00 %
of the nominal/declared
supply voltage
100.0 % to 10 000.0 % of the nominal/de-
clared supply voltage
0.0 V to 1 000 000.0 V
Hysteresis 2.00 %
of the nominal/declared
supply voltage
0.0 % to 50.0 % of the nominal/declared
supply voltage
Detection mode
1)
ph-N ph-N
ph-ph
Current trigger limits
Trigger active no no
yes
Tolerance unit Percentage Percentage
Numerical
Lower threshold 90.00 %
of nominal current In
0.00 % to 99.99 % of of nominal current In
0.0 A to 1 000 000.0 A
Upper threshold 110.00 %
of nominal current In
100.0 % to 10 000.0 % of of nominal
current In
0.0 A to 1 000 000 A
Hysteresis 2.00 %
of nominal current In
0.0 % to 50.0 % of of nominal current In
Configuration binary trigger
Trigger active no no
yes
Trigger source Binary Input 1 Indication 1 from Remote
Indication 2 from Remote
Binary Input 1
Binary Input 2
Trigger value OFF ON
OFF
Waveform capture setting
Total recording duration 2.0 s 0.2 s to 3.0 s in 0.2-s steps
Pretrigger ratio 10 % 0 % to 30 % in 5-% steps
Record ph-ph voltage no no
yes