15 Operating Parameters
15.5 Recording and Reporting
353SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
15.5.3 Recorder Parameters
Parameter Default Setting Setting Range
Measurement recorder
Average intervals - Frequency 10 s fixed
Short term flicker 10 min fixed
Long term flicker 2 h fixed
Average interval - Voltage /
Unbalance / Harmonics
10 min 30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
Record additional data (I, P, Q,
S etc.)
no no
yes
Recorder of average - Min no no
yes
Recorder of average - Max no no
yes
Harmonics parity Odd Even
Odd
All
File generation every:
(corresponds to the setting of
the Average interval parame-
ter)
The created PQDIF files can be
downloaded via the user inter-
face or with the IEC 61850 pro-
tocol.
24 h At average interval File generation
every:
30 s 1 h (fix)
1 min 2 h (fix)
10 min, 15 min,
30 min, 1 h or
2 h
2 h
4 h
6 h
12 h
24 h
Recorded file type PQDIF PQDIF
CSV
All
Flicker lamp model 230 V 230 V
120 V
Trend recorder
Tolerance unit Percentage Percentage
Numerical
Tolerance number Percentage: 3 % of primary
nominal voltage,
Numerical: 0.50 V
1% to 5% in 1-% steps
0.2 V to 500.0 V
Maximum recording interval 10 min 10 min, 30 min,
1 h, 2 h, 4 h, 6 h, 12 h, 24 h