15 Operating Parameters
15.5 Recording and Reporting
354 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
15.5.4 Mains Signalling Voltage
15.5.5 Memory Management
Parameter Default Setting Setting Range
Mains signalling voltage measurement
MSV active no
no
yes
No. of MSV frequencies 1 frequency
1 frequency
2 frequencies
Frequency 1 216.60 Hz 100 Hz to 3 kHz
Frequency 2 1060.00 Hz 100 Hz to 3 kHz
Mains signalling voltage capture setting
Detection threshold 1 % of Udin From 1 % to 15 % of Udin
Total recording duration 75 s 15 s to 120 s in 15-s steps
Pretrigger ratio 10 % 0 % to 30 % in 5-% steps
Parameter Default Setting Setting Range
Memory splitting
Event recorder 1.0 % 1 % to 19 %
Measurement recorder 35.0 %
(the recording time depends on
the aggregation interval)
33 % to 51 %
Trend recorder 47.0 %
(residual storage capacity)
Min. 31 %
Fault recorder 3.0 %
(Numbers of records depends on
the fault-record time)
3 % to 21 %
Mains signalling voltage recorder 14%
(Numbers of records depends on
the record time of the mains sig-
nalling voltage)
14 % to 20 %