15 Operating Parameters
15.5 Recording and Reporting
355SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
15.5.6 Report Configuration
Parameter Default Setting Setting Range
General Information
Company:
Department:
Supervisor:
Inspector:
Location:
Comment:
- Any text displayed in the print-
out of the power quality report
Power Quality Report
Evaluation mode according to: EN 50160 LV&MV EN 50160 LV&MV
EN 50160 HV
User defined
Flagging acc. to
IEC 61000-4-30
no no
yes
Power frequency:
99.5 % of measurement should be in -1.0 % to 1.0 % deviation of the power
frequency.
100 % of measurement should be in -6.0 % to 4.0 % deviation of the power
frequency.
Any setting for user-defined
evaluation mode
Power supply voltage magnitude
95 % of measurement should be in -10.0 % to 10.0 % deviation of the
nominal/declared supply voltage.
100 % of measurement should be in -15.0 % to 10.0 % deviation of the
nominal/declared supply voltage.
Any setting for user-defined
evaluation mode
Voltage unbalance:
1)
95 % of measurement should be less than 2.0 %.
100 % of measurement should be less than 3.0 %.
Any setting for user-defined
evaluation mode
Subgroup Total Harmonic Distortion (THDS):
95 % of measurement should be less than 8.0 %.
Any setting for user-defined
evaluation mode