EasyManua.ls Logo

Siemens SICAM Q100 - Assembly

Siemens SICAM Q100
376 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Getting Started
6.2 Assembly
93SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
6.2.2 Assembly
To install the device into a switch panel, proceed as follows:
Push the device in installation position into the cut-out of the switch panel and hold the device tight.
Attach one of the supplied mounting elements each on both sides of the housing.
Figure 6-2 Stepwise Installation of the SICAM Q100 into a Switch Panel
Swing the mounting element (provided with the device) over the rear cone.
Move the mounting element to the position. Use a screw driver (0.6 mm x 4.5 mm) to fix the mounting
elements until the slipping clutch takes effect.
UL-Certification Conditions
Field Wires of Control Circuits shall be separated from other circuits with respect to the end-use requirements!
Mounting plate
Mounting element
1 mm (0.04 inch), steel
NOTE
The above mounting instructions must be performed correctly to provide sufficient protection against touching
live parts.

Table of Contents

Other manuals for Siemens SICAM Q100

Related product manuals