Address Min/Max Value Parameters Unit Type
1040 0 to 65535 3-phase apparent power 1/10 kVA for 230-V
sensor
uInt16
1/100 MVA for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1041 -1000 to 1000 3-phase power factor – sInt16
1042 -32768 to 32767 3-phase active power 1/10 kW for 230-V
sensor
sInt16
1 kW for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1043 -32768 to 32767 3-phase reactive power 1/10 kVAr for 230-V
sensor
sInt16
1 kVAr for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1044 0 to 65535 3-phase apparent power 1/10 kVA for 230-V
sensor
uInt16
1 kVA for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1045 -2 147 483 648
to
2 147 483 647
Active import energy 1 kWh for 230-V
sensor
uInt32
1046 1 MWh for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1047 -2 147 483 648
to
2 147 483 647
Active export energy 1 kWh for 230-V
sensor
uInt32
1048 1 MWh for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1049 -2 147 483 648
to
2 147 483 647
Reactive import energy 1 kVArh for 230-V
sensor
uInt32
1050 1 MVArh for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1051 -2 147 483 648
to
2 147 483 647
Reactive export energy 1 kVArh for 230-V
sensor
uInt32
1052 1 MVArh for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1053 0 to 65535 Firmware major and maintenance version
number
– uInt16
1054 0 to 65535 Application firmware and build version
number
– uInt16
Modbus Registers
B.2 Implementation of the Modbus Protocol
102 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019