Neutral-Point Displacement Voltage V
NG
> (Group 2)
(Address 45) This register defines the neutral-point displacement voltage. It is expressed in percentage (%).
Refer to Neutral-Point Displacement Voltage V
NG
> (Group 1) , Page 116.
Neutral-Point Displacement Time tV
NG
> (Group 2)
(Address 46) This register defines the neutral-point displacement time. It is expressed in milliseconds.
Refer to Neutral-Point Displacement Time tV
NG
> (Group 1), Page 116.
I
dir
(Group 2)
(Address 47) This register defines the value of ground current for ground-fault detection using the cos φ/sin φ
method. The value is expressed in amperes.
Refer to I
dir
(Group 1) , Page 120
Capacitor Voltage
(Address 48) This register defines the capacitor voltage.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit –
Range 0 (4 V to 30 V)
Default 0 (4 V to 30 V)
Auto Calibration Voltage
(Address 49) This register defines the auto calibration voltage.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit V
Range 1000 to 36 000
Default 20 000
Ground-Current Acquisition
(Address 50) This register defines the ground-current sensor which is either used or not used in the isolated/
resonant-ground connection. If the ground-current sensor is used for isolated/resonant-ground connection,
the ground current is measured. If the ground-current sensor is not used for isolated/resonant-ground connec-
tion, the ground current is calculated.
Bit
15 14 13 12 11 10 9 8
Not used Not used Not used Not used Not used Not used Not used Not used
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
Modbus Registers
B.4 Register-Type Data – Holding Registers
122 SICAM, Feeder Condition Monitor, Manual