Default 0 = Not reversed
P,Q Sign
(Address 59) This register defines the P,Q sign parameter.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 0 to 1
0 = Not reversed
1 = Reversed
Unit
Default 0 = Not reversed
Neutral-Point Treatment (Group 2)
(Address 60) This register defines the neutral-point treatment method.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 0 to 2
0 = Solid
1 = Isolated
2 = Compensated
Default 1 = Isolated
Reserved for future use
(Address 61)
Reserved for future use
(Address 62)
Reserved for future use
(Address 63)
Reserved for future use
(Address 64)
Reserved for future use
(Address 65)
Reserved for future use
(Address 66)
Modbus Registers
B.4 Register-Type Data – Holding Registers
SICAM, Feeder Condition Monitor, Manual 125
E50417-H8940-C580-A4, Edition 03.2019