Reserved for future use
(Address 67)
Reserved for future use
(Address 68)
Reserved for future use
(Address 69)
V< (Under-Voltage Phase Threshold for Ground Fault)
(Address 70) This register defines the under-voltage threshold for exact phase detection in case of a 1-phase-
to-ground fault. This is set as a percentage value of the network rated voltage.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 0 % to 100 %
Default 0
V> (Over-Voltage Phase Threshold for Ground Fault)
(Address 71) This register defines the over-voltage threshold for exact phase detection in case of a 1-phase-to-
ground fault. This is set as percentage value of the network rated voltage.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 100 % to 170 %
Default 0
I
N
Delta Pulse Off-On (3I0 Delta)
(Address 72) This register defines the threshold value of the ground-fault current between pulse ON and pulse
OFF. This register is set as percentage value of the rated ground-current threshold value.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Range 1 to 300
Unit percentage
Default 0
Pulse-on Duration (TPulse On)
(Address 73) This register defines the duration of the pulse ON, in other words the switch-on duration of the
capacitor. It is expressed in milliseconds.
Modbus Registers
B.4 Register-Type Data – Holding Registers
126 SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019