Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit ms
Range 0, 20 to 2000
Default 0
For example, if Modbus value is:
20 = 200 ms
1050 = 10500 ms
Pulse-off Duration (TPulse Off)
(Address 74) This register defines the duration of pulse OFF, in other words switch-off duration of the capac-
itor. It is expressed in milliseconds.
Bit 15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit ms
Range 0, 20 to 2000
Default 0
For example, if Modbus value is:
20 = 200 ms
1050 = 10500 ms
Number of Pulses for Operate (PulseTh Op.)
(Address 75) This register defines the number of pulses to be detected within the pulse monitoring time.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format 16-bit unsigned integer
Unit –
Range 1 to 100
Default 0
Number of Pulses for Monitoring (PulseTh Mon.)
(Address 76) This register defines the number of pulses to be considered for calculating the pulse monitoring
time.
Bit
15 14 13 12 11 10 9 8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit 7 6 5 4 3 2 1 0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Modbus Registers
B.4 Register-Type Data – Holding Registers
SICAM, Feeder Condition Monitor, Manual 127
E50417-H8940-C580-A4, Edition 03.2019