Note
To avoid issuing unintentional door commands, remove the terminals X6 and X5 before
changing the FBLOCK input conguration.
Note
SIDOOR ATD401W
In the delivery state of the control unit ATD401W the "Default input" conguration is specied for
the input signals Input 0 to Input 4 and the parameter for the default command mode (p100) is
set to "FBLOCK + relay".
If the control unit does not respond to input signals, select the desired conguration of the input
signals again in the service menu under "General setup > Special parameters > FBLOCK
conguration".
If the control unit still does not respond to input signals, check whether the standard command
input is set to "FBLOCK + relay" (p100=1) in the service menu under "General setup > Special
parameters > Std. command input".
Note
When the predened FBLOCK congurations are selected for the input signals Input 0 to Input 4,
all FBLOCK parameters as well as the speed and force parameters (p3686 – p3689) for the
"Specic door range of motion" are reset to their default values.
Note
SIDOOR ATD420W / ATD430W
In the state of delivery of the control units with eldbus connection no functions are assigned
to the inputs Input 0 to Input 4. Parameters are assigned via the function blocks (FBLOCK)
(Page 86).
Note
The inputs Input 0 and Input 1 are implemented isolated from the inputs Input 2, Input 3 and
Input 4. Therefore the inputs Input 0 and Input 1 can be connected independently of Input 2,
Input 3 and Input 4 as follows:
1. Connection to the internal 24 V control voltage (see the following gure under a. and c.)
2. Connection to the same or other external control voltages (see following gures under b. and
d.)
Controllers
5.4 Connecting terminals
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA 133