Table 5-21 Startup parameter record byte 3
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
Telegram type parameter
X X X X X Telegram type
The telegram type on the internal bus is set via bits 0 to 2.
The following coding results:
Default telegram = 0000
b
Mirror telegram = 0001
b
Broadcast = 0010
b
Special telegram = 0011
b
Default = default telegram
0 0 0 Reserved
Table 5-22 Startup parameter record bytes 4 and 5
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
Cycle time parameter
0 to 234 (0x00 to 0xEA) Cycle time (high byte)
0 to 96 (0x00 to 0x60) Cycle time (low byte)
The cycle time is given in [ms]. The time range is between 10
and 60000 ms. The cycle time species the minimum time
intervals in which the communication on the internal bus
runs.
The default is 100 ms = 0064
hex
Table 5-23 Startup parameter record bytes 6, 7 and 8
Bit
7
Bit
6
Bit
5
Bit
4
Bit
3
Bit
2
Bit
1
Bit
0
Parameter
0 0 0 0 0 0 0 0 Reserved
Conguration
The resulting conguration data is in the GSD le (see Table 5-15 GSD les (Page 151)).
The structure expected from the PROFINET module is described in the following:
Table 5-24 PROFINET conguration data
Slot Api Subslot Module
ID
Submodule
ID
Description
0 0 0001
hex
1 1 DAP (ATD430W)
0 0 8000
hex
1 2 Interface
0 0 8001
hex
1 3 Port 1
Controllers
5.5 Relay and eldbus interfaces
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA 159