Sources of drive orders
Drive order
source
Description
Service button Activating a service button results an immediate switchover to the local mode (see Local/master operation
(Page 161)). The Deenergize drive order is active where no button is pressed. If the "Stop with disable DCU"
command is active, the controller cannot be operated via the service buttons.
LEARN RUN
OPEN CLOSE
S402 S403S401
S401 (learn run)
If S401 is pressed for approx. 5 s in the Power ON state, the special learn
run (learn run with new motor) drive order is activated. You can nd
additional information in Learn run (Page 46).
The button can be released once the learn run has started. The learn run
can be canceled at any time (see Learn run (Page 46)).
S402
The Open drive order is active as long as the button is pressed.
S403
The Close drive order is active as long as the button is pressed.
SIDOOR functions
4.1 Basic functions
ATD4xxW for industrial applications
58 System Manual, 06/2022, A5E51901827B AA