Digital electronic modules
3.20 2RO NO/NC 24 VDC to 48 VDC/5 A, 24 VAC to 230 VAC/5 A digital electronic module (6ES7132-4HB11-0AB0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
3-85
Data for selecting an actuator
Output current
Continuous thermal current
max. 5 A
Min. load current
8 mA
Connecting two outputs in parallel
for redundant triggering of a load
no
To increase performance
no
Control of a digital input Yes
Switch rate
For resistive load
2 Hz
On inductive load
0.5 Hz
For lamp load
2 Hz
Limitation (internal) of the voltage induced on
circuit interruption
no
Short-circuit protection of the output
1
no
1
The relay outputs must be fused externally with 6 A. For installation in a hazardous area as
specified by the National Electric Code (NEC) the fuse must only be removed with a suitable tool if
the subassembly is not in an explosive area.