EasyManua.ls Logo

Siemens Simantic ET 200S - Table 4-15 SIMATIC S7 Format: Measuring Range Type C in °C and °F

Siemens Simantic ET 200S
274 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog electronic modules
4.2 Analog value representation
ET 200S
4-10 Manual, Edition 10/2005, A5E00514527-01
Measuring range for thermocouple: Type C
Table 4-15 SIMATIC S7 format: Measuring range Type C in °C and °F
Units Units
Type C in °C
Decimal Hexadecima
l
Type C in °F
Decimal Hexadeci
mal
Range
> 2500.0 32767 7FFF
H
> 3276.6 32767 7FFF
H
Overflow
2500.0
:
2315.1
25000
:
23151
61A8
H
:
5A6F
H
3276.6
:
2786.6
32766
:
27866
7FFE
H
:
6CDA
H
Overshoot range
2315.0
:
0.0
23150
:
0
5A6E
H
:
0000
H
2786.5
:
32.0
27865
:
320
6CD9
H
:
0140
H
Rated range
0.1
:
-120.0
-1
:
-1200
FFFF
H
:
FB50
H
31.9
:
-184.0
319
:
-1840
013F
H
:
F8D0
H
Undershoot
range
< -120.0 -32768 8000
H
< -184.0 -32768 8000
H
Underflow
Measuring range for thermocouple type E
Table 4-16 SIMATIC S7 format: Measuring range Type E in °C and °F
Units Units
Type E in °C
Decimal Hexadecima
l
Type E in °F
Decimal Hexadeci
mal
Range
> 1200.0 32767 7FFF
H
> 2192.0 32767 7FFF
H
Overflow
1200.0
:
1000.1
12000
:
10001
2EE0
H
:
2711
H
2192.0
:
1832.1
21920
:
18321
55A0
H
:
4791
H
Overshoot range
1000.0
:
-270.0
10000
:
-2700
2710
H
:
F574
H
1832.0
:
-454.0
18320
:
-4540
4790
H
:
EE44
H
Rated range
< -270.0 - 32768 8000
H
< -454.0 - 32768 8000
H
Underflow

Table of Contents