Analog electronic modules
4.5 Parameters for analog electronic modules
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-27
See also
Connecting Thermocouples (Page 4-18)
4.5.2 Parameters for analog electronic modules 2AI U High Feature and 2AI I 2/4WIRE
High Feature
Table 4-31 Parameters for analog electronic modules U, I High Feature
2AI U High Feature 2AI I 2/4WIRE High Feature Range of values Default setting Applicability
Group diagnosis (parameter assignment error,
internal error)
• disable
• Enable
disable Module
Diagnostics: Overflow/underflow
• disable
• Enable
disable Module
--- Diagnostics: Wire break
1
• disable
• Enable
disable Channel
Smoothing
• None
• Weak
• Medium
• Strong
None Channel
Type/range of
measurement
---
• De-activated
• ± 5 V
• 1 V to 5 V
• ± 10 V
± 10 V Channel
--- Type/range of measurement
• De-activated
• 4 to 20 mA
• ± 20 mA
4 to 20 mA Channel
Interference frequency suppression
• disable
• Enable
disable Module
Run-time calibration
• disable
• Enable
disable Module
1
Only in the measuring range 4 to 20 mA
See also